Generator Control System
FWMurphy
Description
The compact and powerful MGC2000 generator
control system features a unique, simple-to-install
and setup design and enhanced operation.
The control method for the MGC2000 may be
specified for using either the AS3000 Autostart
automatic controller or the 518APH electrically
tripped annunciator method.
The system is available in two basic configurations:
MGC2000
features mechanical gages:
- MGC2000-A Automatic Control: with
Murphy’s AS3000 Generator Controller.
- MGC2000-M Manual Control: with
518APH annunciator control.
Both configurations include standard AC
voltmeter, AC ammeter, and frequency meter.
Available for single-phase, standard three-phase,
and three-phase, re-configurable generators.
MGC2000E
features electric gages:
- MGC2000E-A Automatic Control: with
Murphy’s AS3000 Generator Controller.
- MGC2000E-M Manual Control: with
518APH annunciator control.
Both configurations include standard AC volt-
meter, AC ammeter, and frequency meter.
Available for single-phase, standard three-phase,
and three-phase, re-configurable generators.
Features
Dynamic design allows for easy installation
and full operation flexibility.
1/4 inch quick disconnect terminations
Shock mount assemblies to minimize damage
AC voltmeter and ammeter
Phase selector switch
Frequency meter: 45-65hz
Optional hourmeter; DC Voltmeter;
DC ammeter
First-out fault shutdown and indication
(AutoStart models only) of low oil pressure,
high temperature and auxiliary inputs
Inputs can be from engine-mounted fault
switches or panel-mounted SWICHGAGE
®
instruments.
Magnetic pickup or generator AC speed
sensing (AutoStart models only). For automat-
ic crank release and overspeed fault shutdown.
Speed calibration is automatic–adjustment free.
Additional switch inputs allow optional remote
control of crank disconnect and overspeed fault.
Generator AC Hz meter output: 0-1 mA.
User-friendly: Well-thought-out routine for
faster and easier set up.
Interfaces with existing equipment: functions
seamlessly with many other Murphy instru-
ments and controls (AutoStart models only).
Specifications
Pressure Gage: 100°psi (680 kPa) [7 bar]
Mechanical Gage Pressure Connection: 1/8” NPT.
Electric Gage Pressure Connection: 2-wire.
Temperature Gage: 0-250°F (121°C)
Mechanical Gage Temperature Connection: 12ft.
(3.67 m) capillary tubing and sensing bulb.
Electric Gage Temperature Connection: 2-wire.
Enclosure: 16 Ga CRS powder coated.
Optional NEMA 4X Type Enclosure:
Water and dust tight indoor/outdoor enclosure
intended to protect enclosed equipment against
splashing, seepage, falling or hose-directed
water and severe external condensation.
AC Meters: AC ammeter and an AC voltmeter
and a frequency meter are standard features.
Ranges must be specified.
Single or Three Phase: Specify.
Control Method: may be specified:
- AS3000 Autostart automatic controller or
- 518APH Annunciator control method.
NOTE: Autostart method is highly recommended.
DC Voltage:
12 or 24 volt DC voltage must be specified.
MGC2000
New Dynamic Design Allows for
Easy Installation and Full Operation
Flexibility
Features Murphy’s AS3000 Engine/
Generator Controller
User-Friendly, Well Thought-out
Routine for Faster/Easier Setup
AS3000 Autostart
Generator Controller
Voltmeter
Hourmeter
Pressure Gage
Temperature Gage
Frequency Meter
1 - 3 Phase
Selector Switch
16 ga CRS Enclosure,
NEMA 4 Optional
AC Ammeter
AC Voltmeter
Page view 0
1 2 3 4

Summary of Contents

Page 1 - Generator Control System

MGC-02029BRevised 06-03Catalog Section 75(00-02-0500)Generator Control SystemFWMurphyDescriptionThe compact and powerful MGC2000 generatorcontrol syst

Page 2 - MGC-02029B page 2 of 4

Power supply:• Continuous voltage range: 8-35 VDC• Brown out voltage < 5 VDC for 2 secs (recovery to 8V)• Blackout voltage: 0V for 50mS (from 10V,

Page 3 - MGC2000 System Options

•DC Voltmeter*•DC Ammeter*•Hourmeter*•Relays. 4 relays, wired for Preheat, Crank, Fuel, and Common Alarm•Keyswitch•Phase select switch, standard for 3

Page 4 - 1 – A – 12

MGC-02029B page 4 of 4How to Order the MGC2000Phases1 = Single Phase3 = Three PhaseBase ModelMGC2000= Mechanical GagesMGC2000E = Electric GagesControl