MDM45 Digital Loop Monitor SWICHGAGE
®
Instructions for Installation and Operation
®
MDM-9114N
Revised 06-97
Section 05
(00-02-0160)
Description
The MDM45 is a 4-1/2 in. (114 mm) dial digital loop monitor with low and
high trip points which are adjustable over the full range of the monitor. A tog-
gle switch and a push button are provided in the face of the monitor for easy
access to the trip point adjustments. The MDM45 accepts one 4-20 mA trans-
mitter input. It is designed to operate from 12 or 24 VDC systems.
Specifications
Accuracy: ±1.0% of full scale.
Operating Temperature Range: 32 to 155°F (0 to 70°C).
Storage Temperature: -40 to 300°F (-40 to 150°C).
Case Material: Aluminum.
Display Range: -10,000 to 19,999.
Signal Input: 4–20 mA.
Input Resistance: 250 Ohms.
Display Update Time: 0.5 seconds.
Power Input: 1.8 watts @ 12 VDC; 3.6 watts @ 24 VDC.
Trip Point Output: A power FET switch turns on when signal reaches the trip
point. Trip points can be selected to open or close, (0.5 A @ 250 VDC).
*
Laboratory Approvals: MDM45 is CSA approved for Class I, Division 2,
Group D, hazardous areas. Digital loop monitor input 10–30 VDC, 4–20 mA.
NOTE: MDM45 is for use with Electromechanical TATTLETALE
®
annunci-
ators or SELECTRONIC
®
or similar solid-state annunciators.
About Trip Points
During normal operation, both trip points are always active and are indepen-
dent of the trip point selector switch. When the transmitter signal meets the
high or low trip point, that trip point is triggered: the trip point output “turns
on”, and an LED light to indicate the output is ON.
Open Transmitter Input
An open transmitter input causes the SWICHGAGE
®
to go negative, trigger-
ing the low trip point if the trip point is being used.
Warranty
A two year limited warranty on materials and workmanship is provided with this
Murphy product. Details are available on request and are packed with each unit.
Mounting
The MDM45 has a flush mount case for installation in a panel from 1/32 in.
(1 mm) to 1/8 in. (3 mm) thick. We recommend to install the MDM45 within a
weatherproof enclosure to protect it from rain, dust, etc.
A round mounting hole size 4-3/4 in. (121 mm) diameter is needed for the
mounting. Three (3) screw holes 1/4 in. (6 mm) are also needed to secure
the unit to the panel (See mounting diagram).
With a straight edge screwdriver remove the three (3) screws located in the
front of the unit and install the unit from the back of the panel; secure firmly
in place by tightening the screws.
NOTE: A minimum distance of 12 in. (305 mm) from any ignition coil or
coil leads should be maintained.
Mounting Dimensions
Please read the following information before installing. A visual inspection for any damage which may
have occurred during shipping is recommended. It is your responsibility to have a qualified person install the
unit, and make sure it conforms with NEC and local codes.
GENERAL INFORMATION
Installation Accessories
Straight edge screw driver (medium).
Wire cutters, wire stripping and terminal crimping tool.
Potentiometer trimmer or small screwdriver with plastic handle.
4–20 mA simulator.
DC power supply (10–30 VDC, 150 mA minimum).
Made in USA
®
FRANK W.
MFR.
MDM45
DISPLAY
PUSH TO READ
TRIP POINT
LOW
TRIP PT
HIGH
TRIP PT
®
Approved* for
Class I, Division 2,
Group D Hazardous
Locations
WARNING: Disable the engine (motor) so it can NOT start.
Remove the battery ground cable (when applicable).
1/4 in.
(6 mm)
dia.
3 holes
120
120
120
2-39/64 in.
(66 mm)
radius
Mounting Hole
4-3/4 in. (121 mm)
diameter
panel
side view
WARNING
BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT
Disconnect all electrical power to the machine.
Make sure the machine cannot operate during installation.
Follow all safety warnings of the machine manufacturer.
Read and follow all installation instructions.